The
Riello Galatrek Multi Dialog Uninterruptible Power Supply range is the
ideal solution for computer and telecoms users wanting a flexible
multiple operating format power system with advanced communications
features.
There is a
19" rackmount format product 10-30kVA and version with a built in
isolation transformer for critical applications requiring Galvanic
isolation - 10-20kVA.
10-20kVA
single/single or three/single-phase
10-80kVA three/three-phase
Uninterruptible Power Supply with
multiple operating modes
The Multi
Dialog Uninterruptible Power Supply series UPS uses double conversion
on-line technology (VFI) and has several other operating mode options.
Multi Dialog AF systems incorporate an harmonic filter to achieve less
than 4% harmonic distortion and a near perfect sinewave absorption from
the mains.
In on-line
mode the load is powered continuously by the inverter to remove sags,
surges and brownouts, through EMI filters to suppress transients, spikes
and electrical noise. Even on bypass the load is routed through the
filters so that the load is not connected to raw mains.
When the
mains fails, the inverter which is constantly powering the load simply
draws power from the internal battery to provide complete protection.
UPS Operating Modes
As well as
the its on-line operating mode, Multi Dialog can operate in:
-
Economy Mode:
uses Line Interactive (VI) technology to power less critical loads
from the mains supply for certain periods. The function can be set
from the front panel keypad or remotely using software
-
Smart Active:
if the mains supply is out of range, the UPS will power the load
from the inverter as an On-line UPS. When the mains supply returns
to within range again, the UPS will monitor this for a certain
period before selecting line Interactive operation
-
Standby/Off:
for security applications like emergency lighting where the UPS is
switched on but the loads are powered through the bypass supply.
When the mains fails or falls outside a preset range the inverter
automatically powers the load. This operation is similar to that of
a standby uninterruptible power supply.
-
Frequency conversion:
50 or 60Hz
-
Automatic Voltage Stabiliser:
voltage stabilisation with the inverter and
battery completely disabled.
Extended Runtimes
As the
inverter is rated for continuous operation this type of uninterruptible
power supply can be used to support large loads for long runtimes up to
and over 7 hours or more in duration. This can be achieved using battery
extension packs that connect in series to the rear panel connector on
the UPS and/or a generator. When battery extension packs are used these
may have their own mains powered chargers to maintain a reasonable
recharge time of the complete battery set. For larger loads consider the
Master Dialog.
Whatever
the runtime installed there should be sufficient time for the protected
computer systems to be shutdown in an orderly manner using the
PowerShield² software, supplied as standard, for Windows 95, 98, 2000,
2003, Me, XP, Mac OSx, 9.x, Linux NT 4.0 operating systems. Additional
remote monitoring can be achieved using PowerNetGuard on Wide Area
Networks or the TeleGuard remote service monitoring system with text
alerts for site problems, and the wide range of NetMan SNMP interfaces
and MultiCom adapters available.
Advanced Communication
-
advanced, multi-platform
communication, for all operating systems and network environments:
PowerShield² supervision and shut-down software included, with SNMP
agent, for Windows 95, 98, 2000, 2003, Me, XP, Mac OSx, 9.x, Linux,
NT 4.0, Novell operating systems. The UPS is equipped with a cable
for direct connection to the PC (Plug and Play)
-
double RS232 serial port
-
network adapter slot for SNMP agent
-
EPO (Emergency Power Off) shut down
input contact
-
remote control panel
Features
-
reliable, filtered, stabilised and
regulated sinewave output (double on-line conversion technology VFI
according to EN50091-3 specifications) with filters for atmospheric
disturbance suppression
-
high reliability: IGBT technology,
full microprocessor control with no-break static and manual bypasses
-
0.8 power factor makes Multi Dialog
suitable for powering ICT and industrial loads
-
high level diagnostics: event log
with 128 messages, states, measurements and alarms - available from
the built-in LCD in several languages
-
the UPS may be configured with the
RS232 serial port (flash upgradeable)
-
power factor correction with
sinusoidal input to ensure a low impact on the mains supply for the
single-phase/single-phase series
-
reduced noise levels: high frequency
inverter bridge used (>16 kHz: above audible range)
-
low power consumption up to 92% in
On-line mode due to the use of IGBT technology and up to 98% in the
other operating modes: “Economy Mode”, Smart Active Mode, and
Standby/Off Mode.
-
low harmonic pollution in the Multi
Dialog CLEAN (AF series) the electronic digital (DSP control) active
filter achieve a very low total harmonic distortion (THDi<4%)
-
compact cabinet (internal option)
-
high reliability (failure of the
active filter does not affect UPS operation)
-
high efficiency: the active filter
does not reduce operational efficiency
-
simple to install:
-
capability to connect the UPS
both to single-phase and three-phase mains supplies
-
panel to offset voltage drop down
long cable runs
-
castors for ease of movement
(models 10-30kVA)
-
maximum reliability and power
availability - connect up to 8 units in parallel or N+1 redundancy,
even of different power ratings
-
power factor correction (input power
factor, close to 1)
-
high level battery reliability:
-
automatic battery test
-
recharge compensated for
temperature
-
emergency operation: the UPS can be
set to operate only when the mains fails (for emergency lighting)
-
back feed protection: to avoid energy
feeding back into the mains supply
-
by pass may be deactivated to allow
operation as a frequency converter (at 50 or 60 Hz)
-
easy to maintain (front access)
Click Here
to download
a brochure
Call us now on
01732 770677
or
contact us
|